When reviewing a solar PV technical proposal, you will often see two capacity figures: kWp (DC capacity of the solar panels) and kW or kVA (AC rated output of the inverter). The ratio between the two is known as the DC/AC Ratio (or Inverter Loading Ratio, ILR).
Why Oversize DC Relative to AC?
Solar panels are rated under laboratory Standard Test Conditions (STC: 1,000 W/m² irradiance and 25°C cell temperature). On an Indian rooftop, ambient temperatures regularly exceed 35–42°C, pushing cell temperatures to 60–65°C. Combined with soiling, cable losses, and non-peak sun angles in the morning and late afternoon, a 100 kWp DC array rarely produces a full 100 kW at the inverter terminals.
By pairing a 115 kWp DC array with a 100 kW AC inverter (DC/AC ratio = 1.15):
- The inverter starts earlier in the morning and stays closer to its high-efficiency operating zone longer throughout the day.
- The AC side infrastructure (inverter, AC cables, switchgear, transformer) is utilized more efficiently, lowering the Levelized Cost of Energy (LCOE).
Understanding Inverter Clipping
During brief midday peaks on clear, cool days when DC input exceeds the inverter's maximum AC rating, the inverter safely limits ("clips") output to its rated AC power. A modest DC/AC ratio of 1.10 to 1.25 for rooftop systems typically keeps annual clipping losses under 1–2% while delivering a net increase in total annual energy yield.